The Armored Metal Enclosed Switchgear is a highly reliable and technically advanced power distribution solution designed for enhanced safety and operational efficiency. With a robust structure and integrated protection mechanisms, this switchgear ensures smooth and secure power distribution across various industrial and commercial applications.
Switchgear technical parameters
| Item? | Units? | Parameters? | |
| Rated voltage? | KV? | 40.5 | |
| Rated insulation level? | 1min industrial frequency withstand voltage? | KV? | 95 (isolation break 115)? |
| Lightning impulse withstand voltage (peak) | KV? | 185 (isolation break 115)? | |
| Rated frequency? | Hz? | 50 | |
| Main busbar rated current? | A? | 630~2500 3150※? | |
| Rated short-circuit breaking current? | A? | 31.5 | |
| Rated short-time withstand current (4s)? | KA? | 25 | |
| Rated peak withstand current? | kA? | 31.5 | |
| Auxiliary control circuit rated | V | 25 | |
| ※forced air cooling | |||
ZN85-40.5 vacuum circuit breaker technical parameters
| Item? | Units? | Parameters? | ||
| Rated voltage? | KV | 40.5 | ||
| Rated insulation level? | 1min industrial frequency withstand voltage? | KV | 95 (isolation break 115)? | |
| Lightning impulse withstand voltage (peak) | KV | 185 (isolation break 115)? | ||
| Rated frequency? | Hz | 50 | ||
| Rated current? | A | 630, 1000, 1250, 1600? | 1250、1600、2000、2500、3150※ | |
| Rated short-circuit breaking current? | A | 25 | 31.5 | |
| Rated short-time withstand current (4s)? | kA | 25 | 31.5 | |
| Rated peak withstand current? | kA | 63 | 80 | |
| Rated sequence of operation? | Minute (O) - 0.3s - Combined Minute (CO) - 180s - Combined Minute (CO)? | |||
| Rated short-circuit breaking current number of openings? | Times? | 20 | ||
| Rated cable charging opening current? | A? | 25 | ||
| Rated capacitor bank opening current? | A? | 400 | ||
| Capacitive current opening and closing performance? | level? | C2? | ||
| Closing time? | ms? | 40~100? | ||
| Opening time? | ms? | 30-60? | ||
| Mechanical lifetime | times | 10000 | ||
| ※forced air cooling | ||||
VD4 series vacuum circuit breaker technical parameters
| Item? | Units? | Parameters? | |
| Rated voltage? | KV | 40.5 | |
| Rated insulation level? | 1min industrial frequency withstand voltage? | KV | 95 (isolation break 115)? |
| Lightning impulse withstand voltage (peak) | KV | 185 (isolation break 115)? | |
| Rated frequency? | Hz | 50 | |
| Rated current? | A | 1250, 1600, 2000, 2500, 3150※ | |
| Rated short-circuit breaking current? | A | 31.5 | |
| ※forced air cooling | |||
VD4 series vacuum circuit breaker technical parameters
| Item? | Unit? | Parameters? |
| Rated short-time withstand current (4s)? | KA? | 31.5 |
| Rated peak withstand current? | KA? | 80 |
| Rated operating sequence? | min(O)-0.3s-combine min(CO)-180s-combine min(CO)? | |
| Closing time? | ms | 55~67? |
| Opening time? | ms | 33~45? |
| Arc-firing time? | ms | <15? |
| Opening time | ms | 48~60 |
| ※forced air cooling | ||